2 Zone Conventional Fire Panel
Two Wire fire alarm system Active end of line monitoring and head removal Up to 32 devices per zone (Dependent on Device Loading Unit: DLU) 4 line x 20 character LCD display Ability to differentiate between smoke detector, heat detector or a manual call point alarms Alarm confirmation feature Event log storing up to 500 events 3 enhanced test modes Zone can be configured to day/night detection mode Delay programming options Certified to EN54 2/4 Standards Requires 2 x 12V 3.2Ah batteries (BAT32) Optional extended battery box with capacity for 2 x 12V 7.0Ah batteries

Technical Specification:

Inputs:
Max Detectors Per Zone: Up to 32 Devices (Dependant on Device Loading Units , 160 per Zone)
Power:
Mains Supply : 230VAC, +10%, -15%, 50/60Hz
Operating Voltage : 24vDC (Range 21-31vDC)
Standby Supply: 2 x 12V 3.2Ah S.L.A Battery
Outputs:
Zone : Up to 2 (300mA)
Monitored Sounder Circuits: Up to 2 (250 mA)
Monitored Relay Circuits: Up to 2 (250 mA)
Auxiliary Output: 24vDC (300mA)
Environment:
Working Temperature: 5°C to 40°C
Dimensions : 333 x 333 x 99mm
Weight : 2.25 Kg