4 Zone Two Wire Fire Panel

Save £137.22

Price:
£304.93 £442.15

Inc VAT

Stock:
Only 1 in stock
- +

Order before 2pm for same day dispatch

Description

4 Zone Conventional Fire Panel
Two Wire fire alarm system Active end of line monitoring and head removal Up to 32 devices per zone (Dependent on Device Loading Unit: DLU) 4 line x 20 character LCD display Ability to differentiate between smoke detector, heat detector or a manual call point alarms Alarm confirmation feature RS485 connection to up to 8 repeater panels Event log storing up to 500 events 3 enhanced test modes Zone can be configured to day/night detection mode Delay programming options 4 or 8 zone panel can now be configured to accept conventional devices on zones 5 to 8 with the optional conventional zone card Certified to EN54 2/4 Standards Requires 2 x 12V 3.2Ah batteries (BAT32) Optional extended battery box with capacity for 2 x 12V 7.0Ah batteries

Technical Specification:

Inputs:
Max Detectors Per Zone: Up to 32 Devices (Dependant on Device Loading Units , 160 per Zone)
Power:
Mains Supply : 230VAC, +10%, -15%, 50/60Hz
Operating Voltage : 24vDC (Range 21-31vDC)
Standby Supply: 2 x 12V 3.2Ah S.L.A Battery
Outputs:
Zone : Up to 4 (300mA)
Monitored Sounder Circuits: Up to 2 (250 mA)
Monitored Relay Circuits: Up to 2 (250 mA)
Auxiliary Output: 24vDC (300mA)
Environment:
Working Temperature: 5°C to 40°C
Dimensions : 333 x 333 x 99mm
Weight : 2.28 Kg
Dimensions:

Customer Reviews & Questions

Payment & Security

Amazon American Express Apple Pay Diners Club Discover Google Pay Maestro Mastercard PayPal Shop Pay Union Pay Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

You may also like...

Recently viewed