Description
MAGDUO Input / Output Module
Configure as an input for reporting from other systems or devices Configure as an output to control external systems Built-in End of Line function
Technical Specification:
Dimensions (Combined)):Width: 146mm
Height: 87mm
Depth: 41mm
Dimensions (Back box):
Width: 146mm
Height: 87mm
Depth: 32mm
Temperature Range:
Operating Temperature: -10°C to +45°C
Voltage Ranges:
DC Output from Mains Powered Panel: 25.5 to 35V DC
DC Output from Battery Powered Panel: 20 to 26V DC
Operating Current (Typical):
Quiescent: 0.207 mA
End of line ON if applicable (in addition to Quiescent): 0.080 mA
Active: 22.715 mA
LED Indication:
Output Active LED (Red): On continuously when output active
Status - EOL/Input Active LED: • On continuously when input active • Flash once every 20 secs for normal • Flash once every 5 secs for EOL
Cable :
Max Cable Length to Input: 3 Metres
Power:
Max loading: • 30V DC = 2A • 250V AC 50Hz/60Hz 2A • Max 3A Surge • Fuses: Fuse 1, Fuse 23.15A Anti-surge 20mm Ceramic • 250V AC (eg. Bussman S505-3.15A)
Device Loading Units:
Max Device Loading Units per Zone: 160 DLU
Module : 23 DLU
Ingress Protection :
IP Rating: IP 30
Dimensions: